Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V3.4.0.14
-
Fix Version/s: V3.4.0.15
-
Component/s: None
-
Labels:
-
Account:SPC EthernetIp Slave (SPCETHERNE)
Description
CIP attribute 27 (Steps Removed) of the Time Sync object has 0 as its default value. However, in case a valid PTP clock master detected, this value must be unequal to 0, which is not the case. Currently, attribtue 27 is always 0.
Attachments
Issue Links
- is cloned by
-
PSEISV3-594 [CIP Sync] Time Sync object attribute 27 does not behave correctly (certification issue)
- Closed
- relates to
-
PSEISV3-592 Update to PTP V2.2.0.1
- Closed