Uploaded image for project: 'EtherNet/IP Firmware V3'
  1. EtherNet/IP Firmware V3
  2. PSEISV3-415

Assembly's first transition to Run Status is reflected one cycle too late in the DPM input area

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.4.0.6, V3.4.2.0
    • Fix Version/s: V3.4.0.7, V3.4.2.0, V3.5.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC EthernetIp Slave (SPCETHERNE)

      Description

      When an I/O connection is opened which is modeful in O->T direction and, the Scanner sends I/O frames which indicate an Idle Status of the connection in the first place and then transists that connection to the Run status, toggling of Idle to Run is reflected one cycle too late in the DPM input area (option EIP_AS_OPTION_MAP_RUNIDLE).

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  MBommert Marc Bommert
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: