Uploaded image for project: 'EtherNet/IP Firmware V3'
  1. EtherNet/IP Firmware V3
  2. PSEISV3-406

netX90/4000: Command codes rejected with status codes ERR_HIL_UNKNOWN_COMMAND and ERR_HIL_INVALID_PACKET_LEN are not transformed into confirmation/response command codes

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.4.2.0
    • Fix Version/s: V3.4.3.0 , V3.5.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC EthernetIp Slave (SPCETHERNE)

      Description

      As an example, the valid command code (EIP_OBJECT_MR_REGISTER_REQ) with invalid packet length (0) will be replied to with status code ERR_HIL_INVALID_PACKET_LEN and command code EIP_OBJECT_MR_REGISTER_REQ, but should be replied to with command code EIP_OBJECT_MR_REGISTER_CNF.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  MBommert Marc Bommert
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: