Uploaded image for project: 'EtherNet/IP Firmware V3'
  1. EtherNet/IP Firmware V3
  2. PSEISV3-282

Stack does not implement the Production Inhibit Timer for COS and AO connections

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V3.4.0.0, V3.4.1.0, V3.5.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC EthernetIp Slave (SPCETHERNE)

      Description

      For connection of type "Change Of State" (COS) and "Application Object" (AO) the Production Inhibit Timer must be implemenented. The timer itself is responsible to reduce the network traffic to a minimum in case the host application triggers data production with a high frequency.

      The Production Inhibit Timer is described in CIP Volume 1 Edition 3.22 in chapter 3-4.5.3  "Production Inhibit Timer"

      Currently the host application can flood the network with IO frames (1ms to 2ms interval) althought the production inhibit time is set to e.g. 50ms. It's expected that IO frames are sent not faster than 50ms in that case.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  KMichel Kai Michel
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: