Uploaded image for project: 'EtherNet/IP Firmware V3'
  1. EtherNet/IP Firmware V3
  2. PSEISV3-137

Cyclic communication interrupted by Set attribute

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V3.3.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC EthernetIp Slave (SPCETHERNE)

      Description

      NRP 52-RE is in cyclic communication with a scanner (RPI 10 ms, timeout multiplier 4).
      Non volatile attribute of QoS object is set (class 0x48, instance 1, attribute 2).

      -> Device does not send cyclic frames for 145 ms.
      Scanner stops cyclic communication and restarts it later.
      Also reproducible with other attributes.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  KMichel Kai Michel
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: