[DLR] Wrong source port value in Neighbor Check Response frame

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.1.0.0, V3.2.0.0
    • Fix Version/s: V3.2.0.3, V3.2.1.0, V3.3.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC EthernetIp Slave (SPCETHERNE)

      Description

      The source port field within the Neighbor Check Response frame shall hold the port number (1, 2) from which the response frame is sent.
      Instead of using value 1 or 2 to indicate the appropriate port number, the stack uses values 0 and 1.