Description
OWNED and CONFIGURED bit are not set in STATUS word ID object (class 1, attrib. 5)
The STATUS word, however, is supported but the OWNED and CONFIGURED bits are not set by the EIS stack. According to the specification the bits need to be set, if
- (OWNED) the device has an owner; typically this will be due to the device being an end point of an I/O connection.
- (CONFIGURED) the application of the device has been configured to do something different than the “out–of–box” default.
See: Volume 1: Common Industrial Protocol Specification, Chapter 5A: Object Library Part A
Identity Object, Class Code: 0x01, Table 5A-2.3 Bit Definitions for Status Instance Attribute of Identity Object
Attachments
Issue Links
- blocks
-
PSEIPCORE-190 Make device Status bits 0 "Owned" and 2 "Configured" (Identity Object, Attribute 5) settable by application