Uploaded image for project: 'EtherNet/IP Adapter V2'
  1. EtherNet/IP Adapter V2
  2. PSEIS-924

Network status LED does not indicate "Connection Timeout" when unplugging the ethernet cable.

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.13.0.8
    • Fix Version/s: V2.13.0.9, V2.13.1.0, V2.14.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC EthernetIp Slave (SPCETHERNE)

      Description

      For an Exclusive Owner connection, the network status LED is supposed to indicate "Connection Timeout" (flashing red) in case the conenction times out for some reason. This works as long as the device has an active ethernet link. It does not work in case the ethernet cable is is disconnected from the device. In that scenario the network LED switches to OFF.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  KMichel Kai Michel
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: