Firmware sets Encapsulation Inactivity Timeout value to 0 when using command EIP_APS_SET_CONFIGURATION_PARAMETERS_REQ (0x3612) for configuration (certification issue)

    Details

    • Account:
      SPC EthernetIp Slave (SPCETHERNE)

      Description

      Firmware sets Encapsulation Inactivity Timeout value to 0 (TCP/IP Interface object 0xF5, attribute 13) when using command EIP_APS_SET_CONFIGURATION_PARAMETERS_REQ (0x3612) for configuration.

      Workaround: After the device started up the first time, set the encapuslation inactivity timeout value (attribute 13 of class 0xF5) manually to the value of 120.