Details
Description
When the connection configuration editing session is ended with the Change_Complete service (Service Code 0x51) and Change-Type set to 0 ("Full"), the scanner does not stop all connections as expected when using this chage-type.
Instead, it stops and reinitialize only the connection for which the parameters have been changed during the editing session.