Details
-
Type: Change
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: None
-
Fix Version/s: V3.7.5.0
-
Component/s: None
-
Labels:None
-
Account:SPC EthernetIp Core (SPCETHERNET)
Description
Currently the pre-consumption timeout is implemented with a fixed value of 10 seconds. According to CIP Vol1 3-4.5.2, the pre-consumption timeout shall have a value of either:
- 10 seconds or
- expected packet rate multiplied by the connection timeout multiplier
depending on which value is numerically greater.
This also makes the implementation more robust against not seeing the first I/O frame, which in combination with a RPI >= 10 seconds can lead to the consumption timeout today.
Attachments
Issue Links
- discovered by
-
PSEIP-577 Extend maximum RPI from 1 second to 32.767 seconds
- Closed