Details
Description
When a missing slave is reconnected and enters cyclic communication, sometimes diagnosis is not updated.
Error flag stays set.
Communication Error stays set with value TLR_E_CONNECTION_TIMEOUT (0xC0000142).
"Active slaves" is not updated.
"Slaves with diagnostics" is not updated.
RCX_GET_SLAVE_HANDLE_REQ (0x00002F08) returns correct information about active and faulted slaves in this situation.
Attachments
Issue Links
- relates to
 - 
                    
PSEIPCORE-56 Diagnosis information in connection indication (0x1A2E) sometimes not correct when a slave is connected (EtherNet/IP scanner only)
-         
 - Closed
 
 -         
 - 
                    
        
        PSEIM-420
        Update to EtherNet/IP Core V2.0.7.0 
    
-         
 - Closed
 
 -