Uploaded image for project: 'EtherNet/IP Scanner'
  1. EtherNet/IP Scanner
  2. PSEIM-342

EIP_OBJECT_CONNECTION_IND packet holds wrong packet length

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.6.4.0
    • Fix Version/s: V2.6.5.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC EthernetIp Master (SPCETHERNETMA)

      Description

      The packet EIP_OBJECT_CONNECTION_IND holds a wrong packet length of 84 (should be 83).
      This is due to a structure inside the packet data (EIP_OBJECT_EXT_CONNECTION_INFO_T) that is not packed.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  KMichel Kai Michel
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: