Uploaded image for project: 'EtherCAT Master V4'
  1. EtherCAT Master V4
  2. PSECMV4-571

Redundancy logic does not work correctly when redundancy port is not explicitly configured

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V4.4.0.0
    • Fix Version/s: V4.4.0.5, V4.4.1.0, V4.5.0.0
    • Labels:
      None
    • Account:
      SPC EtherCat Master (SPCETHERCATMA)

      Description

      Redundancy logic does not work correctly when redundancy port is not explicitly configured

       

      Possible workaround scan in the topology including connected redundancy port.

       

      Testing scenario:

      1. Boot up to OP with configuration not containing Redundancy Port explicitly

      2. Powercycle first slave

      It should come back to up but does not.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  SBormann Sven Bormann
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: