Uploaded image for project: 'Driver Ethernet'
  1. Driver Ethernet
  2. PSDRVETH-48

MRP Test, Control an In Control frames not filtered

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V1.2.0.0
    • Fix Version/s: V1.2.5.0
    • Component/s: PnC Switch Adapter
    • Labels:
      None
    • Account:
      SPC Driver Ethernet (SPCDRIVERE)

      Description

      The Profinet Controller Xc Switch always forwards all MRP Frames to the Opposite Port. According to Profinet Specification it is required that MRP frames are filtered in MRP Manager mode and forwarded in MRP Client mode. As both modes shall be supported by Profinet IRT Controller firmware a configurable frame filtering is required.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  AMesser Andreas Messer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: