Uploaded image for project: 'PROFIBUS Slave'
  1. PROFIBUS Slave
  2. PSDPS-420

Init_Ms0_req reference->reads uninitialized pointer

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.6.4.0
    • Fix Version/s: V2.7.8.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC Profibus Slave (SPCPROFIBUSSL)

      Description

      On PROFIBUS_FSPMS_CMD_INIT_MS0_REQ the IO length check in AP-Task is calulated from uninitialized pointer which can cause error TLR_E_DATA_SET_MISMATCH and worst case netX to stop excecuting

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  mark mark
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: