wrong alarmhandling if master sends unexpected alarm ack after configure prior data exchange

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V2.7.1.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC Profibus Slave (SPCPROFIBUSSL)

      Description

      If master sends GetDiag -> SetPrm -> ChkCfg -> GetDiag and then directly sends AlarmAck without outstanding alarm, the slave does not Leave Master.