With existing config.nxd SetConfig is accepted but not used

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: v2.4.5.0
    • Fix Version/s: V2.7.2.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC Profibus Slave (SPCPROFIBUSSL)

      Description

      1. When there is a config.nxd file, send PROFIBUS_APS_SET_CONFIGURATION_REQ. Confirmation shows no error.
      2. Perform Channel Init.
      Configuration from config.nxd is used.

      I would expect some error in PROFIBUS_APS_SET_CONFIGURATION_CNF, maybe TLR_E_CONFIGURATION_FAULT or TLR_E_PROFIBUS_APS_ALREADY_CONFIGURED.