Uploaded image for project: 'PROFIBUS Master'
  1. PROFIBUS Master
  2. PSDPM-412

FSPMM2 indications overwrite registered application queue

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V2.6.6.0
    • Fix Version/s: V2.6.7.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC Profibus Master (SPCPROFIBUSMA)

      Description

      The indications PROFIBUS_FSPMM2_CMD_EVENT_IND, PROFIBUS_FSPMM2_CMD_CLOSED_IND, PROFIBUS_FSPMM2_CMD_FAULT_IND, PROFIBUS_FSPMM2_CMD_ABORT_IND and PROFIBUS_FSPMM2_CMD_REJECT_IND overwrite the registered application queue.
      The result is that after receiving an indication of type described above, no indications from the stack can be received by application.

      This affects the indication PROFIBUS_FSPMM_CMD_ALARM_NOTIFICATION_IND.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  mark mark
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: