Uploaded image for project: 'DeviceNet Slave'
  1. DeviceNet Slave
  2. PSDNS-394

RCX_SET_FW_PARAMETER_REQ does not change baud rate if address is also set

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V2.3.19.0
    • Fix Version/s: V2.3.19.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC DeviceNet Slave (SPCDEVICESL)

      Description

      Configure slave with controlled release of communication, 250 kbit/s, address 1.
      Set baud rate 500 kbit/s and address 2 by RCX_SET_FW_PARAMETER_REQ (2 requests).
      Set Bus state On.

      Slave starts sending at 250 kbit/s with MAC id 2.