Baud Rate value displayed in diagnosis is not always the currently active one.

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.3.15.0
    • Fix Version/s: V2.3.18.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC DeviceNet Slave (SPCDEVICESL)

      Description

      Baud Rate value displayed in the Extended Diagnosis -> DNS_FAL -> DNS Common Status is not always the currently active one.
      When the Baud Rate is changed by a remote access, the new value is immediately visualized in the DNS Common Status, inspite of the fact that it is not still activated - the stack will use the new value only after a channel init. So, in that sitaution the stack uses the old baud rate value, but its online diagnosis shows the new one, which according to me is not a correct behaviour.