Details
Description
COMX100 CA-DN running the current COMXDNS FW V2.3.19.0 can not be configured via netX Configuration Tool. INIBATCH.nxd is downloaded to the device and it is reset after that, but "Not data base available. (0xC0630005)" communication error is displayed in the Diagnostic window.
Be advised that, when using COMXDNS FW V2.3.9.0 from the previously released Communication Solutions DVD 1.350.120628, the device is successfully configured by the same INIBATCH.nxd
Attachments
Issue Links
- relates to
-
PSDNS-391 Check validity of product identity only when corresponding bit in ulEnableFlags are set in DNS_FAL_CMD_INIT_STACK_REQ.
-