Details
-
Type: Bug
-
Status: Resolved
-
Priority: Major
-
Resolution: Fixed
-
Affects Version/s: V1.0800.3.7940
-
Fix Version/s: V1.0800.3.8323, V1.0800.3.9211
-
Component/s: APP
-
Labels:None
-
Account:SUI User Tools Utilities (SUIUSERTOO)
Description
At the moment it is possible to enter different values for "Type of Station" and "Device Type" in a PROFINET configuration. This is not conform to the PROFINET specification.
Solution proposal:
It should only be possible to edit the field "Device Type". The field "Type of Station" should be greyed out (not changeable anymore) and should diplay the same value entered in the "Device Type" field.
Field "DeviceType" is a NULL terminated string and should not be padded with space characters as in the actual configuration.