Details

    • Type: Change
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V2.4.5.0, V2.5.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      PROD netIC (PRODNETIC)

      Description

      Update Modbus RTU to V1.6.0.0 with new command table configuration option for Change Data transfer trigger mode.

      Following two seperate transfer modes in the Command Table for writing Commands are configureable with the latest netX Configuration tool.

      • “Changed Data” (default)

        • each changing data is written to connected modbus slave

        • the first write command at startup is send to the connected modbus slave on changed data  from "zero" to "none-zero"

      • “Change Data + Initialisation”

        • each changing data is written to connected modbus slave
        • at startup a "zero" value is send to the connected modbus slave to initialise the slave register to zero at start.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    ynikolov Yordan Nikolov
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: