Details
-
Type: Bug
-
Status: Closed
-
Priority: Major
-
Resolution: Fixed
-
Affects Version/s: V2.0.0.6
-
Fix Version/s: V2.0.0.7
-
Component/s: None
-
Labels:None
-
Account:PROD netIC (PRODNETIC)
Description
Configure Open Modbus TCP on NIC 52-RE.
Connect a Modbus RTU client.
Enable Watchdog (Register 1999 = 0x0400).
Disconnect Modbus RTU client.
Sometimes NIC 52-RE freezes, no connection possible on Modbus RTU, Modbus TCP and in netX Configuration tool.