      Description

      Default OMB configuration was modified:

      Page Parameter Value
      Configuration IP address 192.168.0.2
        Netmask 255.255.255.0
        Gateway 192.168.0.100
      Modbus RTU Baud rate 115200
      Web / FTP Web Server Enabled
        FTP Server Enabled

      After downloading configuration to NIC 52-RE, power cycle netIC.
      SYS led stays yellow, COM led green.

      To recover netIC, configuration has to be deleted with ComProX2 in boot loader mode.