Test Bug: Station name is not applied to the new GSDML

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V1.1100.6.9876, V2.0100.7.2186
    • Component/s: DTM
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      Bug Description from Tester:

      The station name is not saved to the newly created GSDML, this crating an invalid DTM

      Steps to reproduce:

      1. Instantiate a netPROXY DTM
      2. Change the station name in PNS configuration page
      3. Export and Import the new GSDML 
      4. Instantiate the new DTM to a PNIO Controller bus line 
      5. Validate the station name in the newly created DTM

      Expected results:

      Station name is the same in the PNS configuration page of the netPROXY DTM

      Actual result:

      The name is not saved to the new GSDML, substituting it with the default name 'nt100reproxy'