Details
-
Type: Change
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: None
-
Fix Version/s: V1.1100.5.4070, V2.0100.6.1097
-
Component/s: DTM
-
Labels:None
-
Account:SPC Profinet Slave (SPCPROFINE)
Description
This issue is is only relevant if the DTM is running in context of a NT 151-CCIES/PNS gateway.
The Create NT 151-CCIES/PNS has a slot 1 with
- sublot 1 for output data
- sublot 2 for input data
- sublot 5 for input data (4 bytes status information)
Only these 3 submodule can be used. The use cannot add another submodule. these 3 submodule are to be used with ONE controller.
As a result SharedDevice makes no sense and the GSDML should have SharedDevice = false