Uploaded image for project: 'PROFINET IO IRT-Controller DTM'
  1. PROFINET IO IRT-Controller DTM
  2. DTMV1PNCIRT-239

RT send clock should not be smaller then IRT send clock

    Details

    • Sprint:
      SYCON.NET_SP_16_5
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      If IRT mode is used for at least one AR, the minimum possible send clock for RT mode is additionally limited to greater or equal values than the send clock of  that IRT AR.
       

      Solution:

      Add validation rule before creating TLV database.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  MKrifka Markus Krifka
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: