Invalid IO configuration in case of loading old projects

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V1.1100.5.6289
    • Fix Version/s: V1.1100.5.8006, V2.0000.6.873
    • Component/s: DTM
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      The meaning of the attribute "length" of an IO signal was changed.

      Up to SYCON.net <= V1.400 "lenght" was used for the length definition of the data type string. for all other data types the value was set to 0.

      Starting with SYCON.net >= 1.500 "lenght" describes the number of array elements of a data type.

       

      An array index with the value 0 means that no IO information is generated in the database and address table. This results in a incnsistent datamodel.

       

      Solution is to change the data length to the default value of 1 in case of loading an old project with data length = 0.