Uploaded image for project: 'PROFINET IO-Controller DTM'
  1. PROFINET IO-Controller DTM
  2. DTMV1PNC-327

Network Scan failed / devices with a empty/undefined profile is not supported

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V1.1100.4.5614, V1.1000.4.5698
    • Component/s: DTM
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      Network scan failed in case of scanning a notebook with Siemens-TIA Portal installed.

      The PNIO role for such a "device" is empty/not any bits are set.

       

      Supported roles are:

      #define PNIO_DEVICE_ROLE_IOD            (0x01)  /**< IO-Device */
      #define PNIO_DEVICE_ROLE_IOC            (0x02)  /**< IO-Controller */
      #define PNIO_DEVICE_ROLE_IOC_IOD        (0x03)  /**< IO-Controller & IO-Device */
      #define PNIO_DEVICE_ROLE_IOM            (0x04)  /**< IO-Multidevice */
      #define PNIO_DEVICE_ROLE_IOS            (0x08)  /**< IO-Supervisor */

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    MKrifka Markus Krifka
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: