      Description

      The error occurs in the mapping dialog.

      Steps to reproduce

      - Import GSDML file (GSDML-V2.32-Keyence-SR-2000-20170110.xml)

      - Reload catalog

      - Insert NT 50-XX-XX

      - Open gateway configuration (settings)

        Select X2 Profibus slave

        Select X3 PROFINET IO Controller

      - Close Save and Dialog

      - Insert SR-2000X devices

      - Open gateway configuration

      - Open signal configuration

      --> on the right side Port X3 there is in the module "Latch and Error Clear Controlbits <Slot10>" no signal

       

      -> With a modified GSDML file a signal can be selected there.

       

      We have changed only one thing in the GSDML file.

      This module is an Unsigned8 and this Unsigned8 contains 2 bits -> usedasbits in the GSDML file.

      one bit is on bitpos 1 and the other on bitpos 7. this is original and the byte is not shown from the PDI in the mapping dialog.

      With the change of the bitpos of the first bit from 1 to 0 1 byte is now displayed in the mapping dialog.