Uploaded image for project: 'netGATEWAY DTM'
  1. netGATEWAY DTM
  2. DTMV1NETGW-1082

NT 151 -BRIN devices not loaded correctly + incorrect product code in ECS

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V1.1100.6.9871, V2.0000.9.1535
    • Component/s: DTM
    • Labels:
      None

      Description

      First issue

      1. Drug and drop BRIN DTM and it shows correct name netTAP[NT 151-RE-RE/ECS/EIS-BRIN]

      2. Save as it is  and Close SYCON.net

      3. Open saved project file and it still shows correct netTAP[NT 151-RE-RE/ECS/EIS-BRIN]

      4. Right Click and the name is changed to netTAP[NT 151-RE-RE/ECS/EIS]

      Automatic signal mapping cannot be done correctly.

      Status is automatically mapped but other signals are not mapped.

       

      Second issue

      - Product codes are opposite

      NT 151-RE-RE/ECS/EIS-BRIN: Current: 0x32020F01 --> Please correct to 0x32021001

      NT 151-RE-RE/ECS/PNS-BRIN: Current: 0x32021001 --> Please correct to 0x32020F01

       

      Third issue

      200 bytes can not be mapped in ECS/PNS because of status bytes - increase the max possible size so that actual 200 bytes can be mapped.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    mminchev Martin Minchev
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: