Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: None
-
Fix Version/s: V1.1100.5.6661, V2.0000.9.1535
-
Component/s: DTM
-
Labels:None
-
Account:PROD netGATEWAY (PRODNETGATEWAY)
-
Epic Link:
Description
Steps to reproduce:
1. Open the attached project.
2. Check the PROFINET IO sizes - its 1430/1024 and 1426/1024.
3. Try adding a new coupler variable.
Expected result:
A coupler variable should be added.
Current result:
A message is shown that the maximum is reached.
The max size for input and output in profinet should be 1432. Inputs have 4 bytes predefined which leaves 1428 that should come from the coupler variables.