Configuration Check option is set to DPV1 specific value for DPV0 slave

    Details

    • Type: Bug
    • Status: Resolved
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V3.0500.10.78
    • Component/s: DTM
    • Labels:
    • Account:
      SPC Profibus Slave (SPCPROFIBUSSL)

      Description

      Add slave "S-Series MFM" (BIMF5861.gsd) to master, open General page.
      Option Configuration Check is set to "Slave shall allow vendor-specific check.".

      This option is only defined for DPV1 slaves.
      "S-Series MFM" is DPV0 and uses the extended parameters for device specific settings.