Uploaded image for project: 'DeviceNet Generic Slave DTM'
  1. DeviceNet Generic Slave DTM
  2. DTMV1DNG-82

Wrong producer data size validation in Bit-Strobe mode

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V1.0102.1.8250, V1.0105.3.4120
    • Fix Version/s: V1.0106.3.5838
    • Component/s: DTM
    • Labels:
      None
    • Account:
      SPC DeviceNet Slave (SPCDEVICESL)

      Description

      Production size are limited up to the 255 bytes while correct value are 8

      tested with Hilscher CIFX50-DN generic Slave

      referring to cfg help page :

      The data that can be sent back from each Slave after a bit strobe command was received is limited to 8 bytes in length.