Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V1.1.360.35808
-
Fix Version/s: V1.2.72.36459
-
Labels:None
-
Account:SUI Sycon (SUISYCON)
Description
1. Create a new project.
2. Add PN controller "CIFX RE/PNM V3".
3. Add EDS based device "CIFX RE/PNS V3.5.35 - V3.x" to PROFINET_IO (any IRT capable device should do).
4. Right click controller, select "Additional functions / Topology Editor".
5. In Topology Editor connect ethernet ports of controller and device together.
6. Select controller and set "Synchronization role" = "Synchronized (IRT) master".
7. Select device and set "Synchronization role" = "Synchronized (IRT) slave".
8. Close Topology Editor.
9. Assign controller DTM to hardware in "Settings / Device Assignment".
10. Download configuration to controller.
11. Open controller's diagnosis.
It shows "Communication error" = "General configuration fault. (0xC0000120)".
12. Goto "Extended Diagnosis / PNM_AP / Configuration state".
It shows "Last configuration error code" = "0xC0CB000A".
-> PNM_AP_CFG_INVALID_DOMAIN_NAME
13. Disconnect controller DTM.
14. Open "PROFINET_IO / Settings / Station Timing".
15. Modify the value of "Sync domain name" and close window with OK.
16. Download configuration to controller.
Now PN controller is configured.
Attachments
Issue Links
- is blocked by
-
DTMV1PNCIRT-453 Invalid Sync-Domain-Name after activating IRT mode for a device
- Closed